The Ventostat 8008 is designed for in-duct
sampling using a pitot sampling tube that is inserted
into the duct. The primary application for this sensor
is Demand Control Ventilation (DCV) in buildings.
Typical applications for the 8008
include office buildings, conference rooms, schools,
retail stores, restaurants, gymnasiums and theaters.
Specifications:
Measurement
Range
0-2000 ppm factory
default Adjustable to 10,000 ppm.
|
Power
18-30 VAC RMS, 50/60 Hz
-half-wave rectified 18-42 VDC polarity
protected 1.75 VA max avr power 2.75 VA peak
power |

|
Agency
Certification
FCC Part 15 Class B / CE
Black Case
UL94-5V Rated |
Analog
Output (Simultaneous)
0-10 VDC (100 Ohms output
impedance)
4-20 mA
(RLmax = 500 Ohms) |
Elevation
(Pressure) Correction
Add 0.13% of reading per mm
Hg decrease from 760 mm Hg (On-board correction,
user set with UIP software), preset at
sea level |
Relay
Output
Normally Open & Normally
Closed (wire either way),
gold bifurcated, 2A max. @ 24VAC.
Adjustable setpoint (with UIP software kit),
factory set at 1000 ppm, 50 ppm hysteresis |
Operating Conditions
15-32°C (60-90oF)
0 – 95% RH,
non-condensing
|
Wiring
18-28 AWG stranded copper
wire only.
2 wires each for power, analog output, relay |
Accuracy
±75ppm or 7% whichever is
greater |
Digital I/O
RS-232 interface for use with
optional PC software and cable in UIP kit
2072 |
Response
Time
0-90% <1 minute |
Warranty
18
months parts and labor Calibration 5-year
guarantee |
Warm-Up
Time
@ 25°C <2 minutes |
Storage
Temperature
-40 – 70°C |
|
|
|
Model Type Number |
Description & Features |
Price |
|
Ventostat 8008 |
CO2
Pitot Duct Sample Controller |
£ 167.00 |
|