Telaire Ventostat 8001B/8002B CO2 Controller

The Telaire Ventostat 8001B/8002B wall or duct mounting CO2 sensors and controllers are designed for Demand Control Ventilation (DCV) in buildings and are suitable for mounting directly inside the ductwork. This approach, using CO2 as an indicator of occupancy, allows ventilation based on actual occupancy while still maintaining ASHRAE recommended per-person ventilation rates. Over ventilation can be reduced, energy can be saved and air quality can be optimised.

All Ventostat Controls are provided with dual analog outputs (0-10 V and 4-20 mA), mounting/wiring sub-base and a 5 year calibration guarantee (more information provided with product). All 8000 series have a DPST relay (normally open or closed) and can be custom programmed to a specific measurement and output range using the UIP PC based software interface or on-board keypad (Display units only).

Specifications:

Measurement Range
0-2000 ppm factory default.
Adjustable to 10,000 ppm.

Agency Certification
FCC Part 15 Class B / CE
Black Case - UL94-5V Rated

Elevation (Pressure) Correction
Add 0.13% of reading per mm Hg decrease from 760 mm Hg
(On-board correction, user set with UIP software),
preset at sea level

Operating Conditions
0-50°C (32-120oF)
0 – 95% RH, non-condensing

Accuracy
±40ppm or 3% whichever is greater

Response Time
0-90% <2 minute

Warm-Up Time
<2 minutes (operational)

Storage Temperature
-20 – 70°C

Power
18-30 VAC RMS, 50/60 Hz -half-wave rectified 18-42 VDC polarity protected 1.75 VA max avr power 2.75 VA peak power

Analog Output (Simultaneous)
0-10 VDC (100 Ohms output impedance)
4-20 mA (RLmax = 500 Ohms)

Relay Output
Normally Open & Normally Closed (wire either way),
gold bifurcated, 2A max. @ 24VAC.
Adjustable setpoint (with UIP software kit),
factory set at 1000 ppm, 50 ppm hysteresis

Wiring
18-28 AWG stranded copper wire only.
2 wires each for power, analog output, relay

Digital I/O
RS-232 interface for use with optional PC software and cable in UIP kit 2072

Warranty
18 months parts and labor Calibration 5-year calibration guarantee

Method
Single Beam Absorption Infrared™
Diffusion sample method

Sample Method
Diffusion or flow through (50 - 100 ml/min)



   
Model Type  Number Product Description and Features Price
Ventostat 8001B Wall or Duct Mounted CO2 Sensor and Controller - No Display.
Conformal coated electronics and high temperature enclosure - UL94-5V
£ 152.00
Ventostat 8002B Wall Mounted CO2 Sensor and Controller - With Display & Keypad.
Conformal coated electronics and high temperature enclosure - UL94-5V
£ 159.00

  8001B/8002B Brochure 

 

 

Contact Us